Electrical Tester
A slim shape design with an easy hand operated switch and button. The ET800 provides an inventive open jaw technology for measuring AC current without opening the clamp jaw. The unit automatically measures ACV, DCV, OHM and ACA by just turning on the meter. The ET800 also has an in-built test lead storage with probe holders for two pole voltage testing applications.
AC Voltage
Range: 0 - 600 V
Resolution: 1V
Basic Accuracy: ¡Ó (1.5% + 3d)
Frequency Range: 40Hz ~ 500Hz
Overload Protection: 600V AC rms
DC Voltage
Range: 0 - 600 V
Resolution: 1V
Basic Accuracy: ¡Ó (1.0% + 2d)
Overload Protection: 600V DC
AC Current
Range: 0 - 200A
Resolution: 0.1A
Basic Accuracy: ¡Ó (3.0% + 3d)
Frequency Range: 45Hz ~ 66Hz
Overload Protection: 200A
Ohm
Range: 0 - 2000Ohm
Resolution: 1Ă
Basic Accuracy: ¡Ó (1% + 2d)
Overload Protection: 600 V rms
General
Sampling Rate: 2.5 times/sec
Overload Indication: OL is displayed for Amps and Ohm functions. Limit value for functions
Continuity Beeper
Threshold: Approx. 25 Ohm ¡V 400 Ohm
Indicator: 2KHz Tone Buzzer
Auto Power Off: Approx 30 minutes
Safety Standard: IEC 61010 ¡V 1 600V CAT III meets UL3111 specifications
Maximum Conductor Size: 12mm dia
Battery Life: 250 hours
Size (W x L x H): 84mm x 175mm x 31mm
Weight: 280g