(3).jpg)
PAT TESTS
Earth Continuity
Test Current: +/- 200mA DC
Display Range: 0.00ohms - 19.99ohms
Pass Value: 0.20ohms
Insulation Resistance
Test Voltages: 500V DC
Display Range: 0.01Mohms - 199Mohms
Pass Value: 1Mohm
Protective Conductor Current
Test Voltage: 230V
Display Range: 0.0mA - 19.99mA
Pass Value: 0.75mA
Touch Current
Test Voltage: 230V
Display Range: 0.00mA - 3.50mA
Pass Value: 0.25mA
IEC Lead Test
Tests Performed: Earth Continuity
Insulation Resistance
Live / Neutral Checks for o/c, s/c and crossed
CIRCUIT TESTS
RCD Trip Time
Test Current: 30mA
Test Current Phase: 0°/180° auto switched
Display Range: 0ms - 500ms
Earth Loop Resistance
Test Current: Non-tripping for >30mA RCD
Display Range: 0.00ohms - 199ohms
Power Socket T