• Other Seaward Sites:

IR800 16th/17th Edition & Part P Tester

IR800 16th/17th Edition & Part P Tester

Hand-Held Insulation Tester

The IR800 is the latest hand – held, battery operated insulation tester incorporating resistance and continuity ranges from the Seaward range. Once again the Seward range offers a number of unique features, including voltage measurements up to 1000AC or DC, a dual safety rating, extensive and a unique robustness, which provides a unique and safer feel.

IR800 is an Electrical Insulation Tester and performs the following measurements:

  • Insulation Resistance from 0.001MW to 2000MW.
  • Low resistance, up to 20W, with a resolution of 0.01W, to meet Part 4 of EN61557.
  • Resistance, with short/open beeper actuated below 30W in a 2000W range.
  • Voltage measurement up to 1000V AC or DC
 
 

Customer Comments

No comments have been made about this product. Be the first to let us know what you think.

Knowledge Base

You must be registered to view Knowledge Base articles related to this product. Please register or log-in to view these articles.

Key Features

  • Regulation Compliance – EN61557 and EN1010 standards. Also, Safety, Environmental and EMC requirements.
  • Rotary Knob – to select:Insulation Resistance, Continuity, Resistance, Voltage, Battery Check.
  • Meets requirements of EN61557-4.
  • Resistance Function – When the unit is placed on ‘Ohms’, the initial mode will be a 2000Ohm range, with short/open bleeper for resistances 30 Ohms.
  • Battery Life is presented on the primary display as a percentage. It is checked using simulated load condition per EN61557.
  • A simple to use, multiple use, lock button is located on the front of the unit.
  • A unique backlight is part of the LCD display and has an on/off button.
  • The tester will auto shut off after 10 minutes, or 30 minutes under locked conditions.
  • The tester will ‘wake-up’ following a number of commands.
  • A beeper is incorporated to let the user know of several conditions during operation, including: detection of voltage AC or DC, the lock feature is activated, a Short/Open beeper will sound during resistance testing when selected and, a single beep will sound during a Test Lead Zero sequence.
  • A ‘Lightening strike’ icon blinks on the display when voltages 30V AC/DC are detected at the inputs in any function.
   

Downloads

Please feel free to download any of the documents associated with this product.

Technical Specification

Insulation Resistance


Auto Ranges: 2.000MW, 20.00MW, 200.0MW, 2000MW

Resolution: 0.001MW on 2.000MW range max

Accuracy: 2% + digits, 2.000MW, 20.00MW, 200.0MW range

Analog Bar Graph: 0 to 1 GW, and infinity

Bar Graph Accuracy: 10%

Test Voltage: 250V; 500V; 1000V

Accuracy: +20% - 0%

Nominal Current: 1mA minimum per EN 61557

Input Protection: 1000V

Voltage Sensing: 0 to 1000V AC/DC to 400 Hz

Audible/ Visable Warning: 30 V AC or DC at inputs

Circuitry protection: Inhibited if 3oV AC or DC at inputs

 

Continuity
 

Accuracy: 2% + 2 counts

Resolution: 0.01W

Open Circuit Test Voltage: 4V DC nominal

Test Current: 200mA, 0 to 2W

Input protection: 1000v

Circuitry Protection: Inhibited if 30 AC or DC inputs

Accuracy: 5% + 2 counts

 

Resolution

 

Resolution: 1W

Test Current: 25mA nominal

Input Protection: 1000V

Voltage sensing: 0 to 100 V AC/DC to 400 Hz

Accuracy: 2% + 2 counts

Audible/Visible Warning: 30 V AC or DC inputs

Knowledge Base

Product Matrix

The Product Matrix allows you to compare the features of up to 5 products. Simply check the box next to the products you wish to compare then select the 'Compare Products' button.

Product Enquiry

Contact Information

indicates required field
Title*
Please type in the validation code from the image (case sensitive).

Additional Information (optional)

 
Site engineered by NorthBloc   
© 2008, Seaward Electronic Group Ltd. All rights reserved.