Q
With reference to Earth Continuity Testing, does the Code Of Practice say that 25 Amps is the preferred test current?
A
No, The IEE code of practice recommends that the user chooses EITHER a low current, 20 - 200mA, (soft) test whilst flexing the cable OR a high current, 1.5 x fuse rating up to 26 Amps (hard) test.